EasyManuals Logo
Home>Huawei>Storage>FusionModule2000-S

Huawei FusionModule2000-S User Manual

Huawei FusionModule2000-S
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #330 background imageLoading...
Page #330 background image
Figure 6-25 Installing a T/H sensor
Step 5 Choose Monitoring > System > ECC800-Pro > Controls and delete the device
failing in communication.
Step 6 Choose Monitoring > Aisle > T/H Sensor Group and check whether the T/H
sensor works properly. If yes, the T/H sensor is functional.
Step 7 Choose Home > Plan View and add a new T/H sensor in the appropriate position.
----End
6.3.17 Replacing a Temperature Sensor
Prerequisites
Recommended tools and materials: diagonal pliers, insulation tape, cable tie,
step ladder (2 m)
A temperature sensor needs to be replaced.
Spare temperature sensors of the same model are available and functional.
Procedure
Step 1 Cut the cable ties on the temperature sensor using diagonal pliers, and remove
the network cable from the temperature sensor.
FusionModule2000-S Smart Modular Data Center
User Manual 6 Operation and Maintenance
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 319

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000-S and is the answer not in the manual?

Huawei FusionModule2000-S Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000-S
CategoryStorage
LanguageEnglish

Related product manuals