5.3.6 Conguring Event Notication
You can set alarm notication by email or SMS as required. Information about a
maximum of 20 users who will receive alarm notication can be displayed.
Prerequisites
To implement alarm
notication by SMS, the following conditions must be met:
● The ECC800-Pro is congured with a 4G module and supports standard SIM
card access.
● The ECC800-Pro is connected to a network with an email server through a
WAN port. Both the Internet and local area network (LAN) are supported.
To use the WeChat notication function, connect the ECC800-Pro to the EDCM system. For
details, see the user guide of the EDCM system.
Procedure
Step 1 Choose System Settings > Event Notication.
Step 2 Set related outbox parameters.
1. Set related parameters in the Outbox Settings area on the Mailbox Settings
page. If the address type of the outbox is Domain name, choose System
Settings > System Parameters, and set related parameters in the DNS
Server Address area on the Monitor IP page.
The DNS server address is provided by the local network operator.
2. Click Test to check the email sending. If an email fails to be sent, check the
outbox settings and DNS Server Address. If the email is sent successfully,
click Submit.
If Test email sending failed is displayed, check whether the receiver's email
server requires CA certicate verication. If it is required, download the CA
certicate from the receiver's email website and upload it in the Mailbox
Certicate area.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning