Figure 5-69 Conguring the alarm linkage policy
----End
5.3.12.5 Commissioning a Network Video Recorder (IVS1800 Scenario)
5.3.12.5.1 Setting Parameters on the IVS1800 WebUI
Context
A default IP address has been
congured for the IVS1800 before delivery. Modify
the IP address based on the actual network plan.
Procedure
Step 1 Check whether the network connection between the PC for logging in to the OMU
portal and the IVS1800 is normal.
If the device is just delivered or has just been restored to factory settings, ensure
that the PC for logging in to the OMU portal is directly connected to the IVS1800
and is in the same network segment as the IVS1800.
For the device that is just delivered or has just been restored to factory settings, its
network information is as follows:
● IP address: 192.168.3.111
● Subnet mask: 255.255.255.0
● Gateway address: 192.168.3.1
Step 2 Enter https://
IP address
:8443 in the address box, and press Enter.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 234