2. On the login page, enter the preset user name admin and preset password
Changeme, set the language, and click Log In.
– After the rst login, change the password in time to ensure account security and
prevent unauthorized network attacks, such as data tampering. The relevant party
will be liable for any security issues caused by the failure to change the preset
password in time or password loss after changing.
– You are advised to change the password periodically.
– Record and keep the password properly. If you forgot the password, you will be
unable to log in to the WebUI.
– When the event
notication is congured and the password retrieval mode is
congured under user management, the password can be retrieved.
– You will be logged out after being inactive for 10 minutes.
– A maximum of three users can log in to the ECC800-Pro WebUI at the same time.
----End
6.3.1.2 Parameter Sync
Procedure
Step 1 After replacing components, log in to the ECC800-Pro WebUI and choose
Maintenance > Parameter Sync to access the parameter synchronization page.
Step 2 Click Device type and select the component type from the drop-down list.
Step 3 Select the failed device in Source Device, select the reserved device in Target
Device, and click Submit to synchronize the
conguration parameters of the
failed device to the reserved device.
----End
6.3.2 Replacing ECC800-Pro Parts
6.3.2.1 Replacing an ECC800-Pro Main Control Module
Prerequisites
● The ECC800-Pro main control module is hot-swappable.
● Before disconnecting cables from the ECC800-Pro main control module, label
the cables based on the corresponding ports.
● Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, label, marker
● Materials: A spare undamaged and undeformed ECC800-Pro main control
module of the same model is available.
FusionModule2000-S Smart Modular Data Center
User Manual 6 Operation and Maintenance
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 301