Step 8 Connect the communications cables and antennas to the ECC800-Pro main control
module.
Step 9 Choose Maintenance >
Conguration File and import the backup conguration
le,
or set parameters for the devices that connect to the ECC800-Pro to ensure
normal communication.
----End
6.3.2.2 Replacing an ECC800-Pro PSU
Prerequisites
Do not touch the terminals in the rear of a removed power supply unit (PSU) to
avoid electric shocks.
● Tool: insulation gloves
● Material: A spare undamaged and undeformed PSU of the same model is
available.
Context
The PSU is hot-swappable.
Procedure
Step 1 Push the locking latch in the upper right corner of the PSU panel leftwards.
Step 2 Pull out the handle of the PSU to remove the PSU from the subrack.
Step 3 Gently push the reserved PSU into the subrack along guide rails, and push the
locking latch rightwards to secure the handle.
Figure 6-8 Replacing a PSU
----End
6.3.2.3 Replacing ECC800-Pro Antennas
FusionModule2000-S Smart Modular Data Center
User Manual 6 Operation and Maintenance