Program features 125
Sleep function for the process PID (PID1) control
The sleep function operates on a 2 ms time level.
The block diagram below illustrates the sleep function enable/disable logic. The sleep
function can be put into use only when the PID control is active.
1) 1 = Activate sleeping
0 = Deactivate sleeping
4022
SelectCompare
1<2
Or
<1
4024
Delay
t
1
2
4023
NOT SEL
DI1
And
&
%refActive
PIDCtrlActive
modulating
Set/Reset
S
R
S/R
NOT SEL
INTERNAL
DI1
4026
Delay
t
Or
<1
StartRq
5320 (B1)
5320 (B2)
1)
INTERNAL
4022
Select
Mot. speed: Actual speed of the motor
%refActive: The % reference (EXT REF2) is in use. See parameter 1102.
PIDCtrlActive: 9902 is PID CTRL.
modulating: The inverter IGBT control is operating.
.
.
.
.
.
.
Compare
1>2
1
2
Output
freq.
0132
4025
4030
Delay
t
Or
<1
Set/Reset
S
R
S/R
2)
2) 1 = Activate sleep boost
0 = Deactivate sleep boost

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)