Page #283 background image
Fieldbus control 283
12
Fieldbus control
Contents of this chapter
The chapter describes how the drive can be controlled by external devices over a
communication network using embedded fieldbus.
System overview
The drive can be connected to an external control system via embedded fieldbus.
The embedded fieldbus supports Modbus RTU, BACnet
®
, Metasys
®
N2 and
APOGEE
®
FLN protocols.
Embedded fieldbus connection is either RS-232 (control panel connector X2) or
EIA-485 (I/O terminals 23…26). The maximum length of the communication cable
with RS-232 is restricted to 3 meters.
RS-232 is designed for a point-to-point application (a single master controlling
one slave).
EIA-485 is designed for a multipoint application (a single master controlling one or
more slaves).

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)