Technical data 389
Fuses and MMPs
Type Fuses MMPs
ACS320- gG UL Class T or
CC (600 V)
Frame I
1N
MMP Type E
Min. Encl.
Vol.
4)
x = E/U
1)
A min A
2)
max A A dm
3
in
3
1-phase U
N
= 200…240 V (200, 208, 220, 230, 240 V)
01x-02A4-2 10 6 10 R0 6.1 MS132-6.3 & S1-M3-25 18.9 1152
01x-04A7-2 16 10 20 R1 11.4 MS165-16
3)
18.9 1152
01x-06A7-2 16/20* 15 25 R1 16.1 MS165-20
3)
18.9 1152
01x-07A5-2 20/25* 15 30 R2 16.8 MS165-20
3)
--
01x-09A8-2 25/35* 15 35 R2 21.0 MS165-25
3)
--
3-phase U
N
= 200240 V (200, 208, 220, 230, 240 V)
03x-02A6-2 10 3 10 R0 4.7 MS132-6.3 & S1-M3-25 18.9 1152
03x-03A9-2 10 6 10 R0 6.7 MS132-10 & S1-M3-25 18.9 1152
03x-05A2-2 10 6 15 R1 8.4 MS132-10 & S1-M3-25 18.9 1152
03x-07A4-2 16 10 15 R1 13.0 MS165-16
3)
18.9 1152
03x-08A3-2 16 10 15 R1 13.2 MS165-16
3)
18.9 1152
03x-10A8-2 16 15 20 R2 15.7 MS165-20
3)
--
03x-14A6-2 25 15 30 R2 23.9 MS165-25
3)
--
03x-19A4-2 25 20 35 R2 27.3 MS165-32
3)
--
03x-26A8-2 63 30 60 R3 45.0 MS165-54
3)
--
03x-34A1-2 80 35 80 R4 55.0 MS165-65
3)
--
03x-50A8-2 100 50 100 R4 76.0 MS495-90 & SK4 &
DX49
--
3-phase U
N
= 380... 480 V (380, 400, 415 V) (MMP ratings for 480Y/277V only)
03x-01A2-4 10 2 10 R0 2.2 MS132-2.5 & S1-M3-25 18.9 1152
03x-01A9-4 10 2 10 R0 3.6 MS132-4.0 & S1-M3-25 18.9 1152
03x-02A4-4 10 3 10 R1 4.1 MS132-6.3 & S1-M3-25 18.9 1152
03x-03A3-4 10 3 10 R1 6.0 MS132-6.3 & S1-M3-25 18.9 1152
03x-04A1-4 16 6 15 R1 6.9 MS132-10 & S1-M3-25 18.9 1152
03x-05A6-4 16 6 15 R1 9.6 MS132-10 & S1-M3-25 18.9 1152
03x-07A3-4 16 6 20 R1 11.6 MS165-16
3)
18.9 1152
03x-08A8-4 20 10 25 R1 13.6 MS165-16
3)
18.9 1152
03x-12A5-4 25 10 30 R3 18.8 MS165-20
3)
--
03x-15A6-4 35 15 35 R3 22.1 MS165-25
3)
--
03x-23A1-4 50 20 50 R3 30.9 MS165-42
3)
--
03x-31A0-4 80 25 80 R4 52.0 MS165-65
3)
--
03x-38A0-4 100 30 100 R4 61.0 MS165-65
3)
--
03x-44A0-4 100 35 100 R4 67.0 MS495-75 & SK4-11 &
DX49
--
3-phase U
N
= 380... 480 V (440, 460, 480 V) (MMP ratings for 480Y/277V only)
03x-01A2-4 10 2 10 R0 1.8 MS132-2.5 & S1-M3-25 18.9 1152
03x-01A9-4 10 2 10 R0 3.0 MS132-4.0 & S1-M3-25 18.9 1152
03x-02A4-4 10 3 10 R1 3.4 MS132-6.3 & S1-M3-25 18.9 1152
03x-03A3-4 10 3 10 R1 5.0 MS132-6.3 & S1-M3-25 18.9 1152
03x-04A1-4 16 6 15 R1 5.8 MS132-10 & S1-M3-25 18.9 1152
03x-05A6-4 16 6 15 R1 8.0 MS132-10 & S1-M3-25 18.9 1152
03x-07A3-4 16 6 20 R1 9.7 MS132-10 & S1-M3-25 18.9 1152
03x-08A8-4 20 10 25 R1 11.0 MS165-16
3)
18.9 1152
03x-12A5-4 25 10 30 R3 16.0 MS165-20
3)
--

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)