Fault tracing 375
Embedded fieldbus faults
Embedded fieldbus faults can be traced by monitoring group Group 53: EFB protocol
parameters. See also fault/alarm SERIAL 1 ERR.
No master device
If there is no master device on line, parameter 5306 EFB OK MESSAGES and 5307
EFB CRC ERRORS values remain unchanged.
What to do:
Check that the network master is connected and properly configured.
Check the cable connection.
Same device address
If two or more devices have the same address, parameter 5307 EFB CRC ERRORS
value increases with every read/write command.
What to do:
Check the device addresses. No two devices on line may have the same address.
Incorrect wiring
If the communication wires are swapped (terminal A on one device is connected to
terminal B on another device), parameter 5306 EFB OK MESSAGES value remains
unchanged and parameter 5307 EFB CRC ERRORS increases.
What to do:
Check the RS-232/485 interface connection.

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)

Related product manuals