Program features 137
Settings
Diagnostics
PFA control
(Requires use of MREL-01 option purchased separately)
PFA control
The pump and fan alternation (PFA) control switches auxiliary pumps on and off as
required by capacity changes. The Autochange function alternates between pumps to
keep the duty times of the pumps equal. Interlocks function enables the drive to
detect if any of the pumps are unavailable (for example, switched off for
maintenance), in which case the next available pump is started instead.
The drive controls the motor of pump 1, varying the motor speed to control the pump
capacity. This motor is the speed regulated motor.
Direct line connections power the motor of pump 2 and pump 3, etc. The drive
switches pump 2 (and then pump 3, etc.) on and off as needed. These motors are
auxiliary motors.
The drive PID control uses two signals: a process reference and an actual value
feedback. The PID controller adjusts the speed (frequency) of the first pump such that
the actual value follows the process reference.
When demand (defined by the process reference) exceeds the first motor’s capacity
(user defined as a frequency limit), the PFA control automatically starts an auxiliary
pump. The PFA control also reduces the speed of the first pump to account for the
auxiliary pump’s addition to total output. Then, as before, the PID controller adjusts
the speed (frequency) of the first pump such that the actual value follows the process
reference. If demand continues to increase, the PFA control adds additional auxiliary
pumps, using the same process.
When demand drops, such that the first pump speed falls below a minimum limit
(user defined by a frequency limit), the PFA control automatically stops an auxiliary
pump. The PFA control also increases the speed of the first pump to account for the
auxiliary pump’s missing output.
An Interlock function (when enabled) identifies off-line (out of service) motors, and the
PFA control skips to the next available motor in the sequence.
Parameter Additional information
Group 64: Load analyzer,
parameters 64016405
Load analyzer settings
Actual signal Additional information
Group 64: Load analyzer,
parameters 64066433
Load analyzer results

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)

Related product manuals