148 Actual signals and parameters
Parameter listing
Parameter data is specific to ACS320 firmware version 4.01C.
Group 99: Start-up data
This group defines special Start-up data required to:
set up the drive
enter motor information.
Note: Parameters checked under the heading “S” can be modified only when the
drive is stopped.
Group 99: Start-up data
Code Description Range Resolution Default S
9901
LANGUAGE
0...25 1 0
Selects the display language.
9902
APPLIC MACRO
-3...21 1 1
Selects an application macro. Application macros automatically edit parameters to
configure the ACS320 for a particular application. See Application macros for
application macro descriptions.
9905
MOTOR NOM VOLT
115 … 345 V (200 V, US)
230 … 690 V (400 V, US)
288 … 862 V (600 V, US)
1 V
1 V
1 V
230 V
460 V
575 V
Defines the nominal motor voltage.
Must equal the value on the motor rating
plate.
Sets the maximum drive output voltage
supplied to the motor.
Drive cannot supply the motor with a
voltage greater than the mains voltage.
9906
MOTOR NOM CURR
0.15*I
2N
… 1.5*I
2N
0.1 A 1.5*I
2N
Defines the nominal motor current.
Must equal the value on the motor rating plate.
0= ENGLISH 1= ENGLISH (AM) 2= DEUTSCH 3= ITALIANO
4= ESPAÑOL 5= PORTUGUES 6= NEDERLANDS 7= FRANCAIS
8= DANSK 9= SUOMI 10= SVENSKA 11= RUSSKI
12= POLSKI 13= TÜRKCE 14= CZECH 15= MAGYAR
16= ELLINIKA 17= CHINESE 18= KOREAN 19= JAPANESE
1= HVAC DEFAULT 2= SUPPLY FAN 3= RETURN FAN 4= CLNG TWR FAN
5= CONDENSER 6= BOOSTER PUMP 7= PUMP ALTERNA 8= INT TIMER
9= INT TIMER CS 10= FLOATING PNT 11= DUAL SETPPID 12= DL SP PID CS
13= E -BYPASS 14= HAND CONTROL 15= E-CLIPSE 21= AC500 MODBUS
Output voltage
Output
9907
frequency
9905

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)