148 Actual signals and parameters
Parameter listing
Parameter data is specific to ACS320 firmware version 4.01C.
Group 99: Start-up data
This group defines special Start-up data required to:
• set up the drive
• enter motor information.
Note: Parameters checked under the heading “S” can be modified only when the
drive is stopped.
Group 99: Start-up data
Code Description Range Resolution Default S
9901
LANGUAGE
0...25 1 0
Selects the display language.
9902
APPLIC MACRO
-3...21 1 1
Selects an application macro. Application macros automatically edit parameters to
configure the ACS320 for a particular application. See Application macros for
application macro descriptions.
9905
MOTOR NOM VOLT
115 … 345 V (200 V, US)
230 … 690 V (400 V, US)
288 … 862 V (600 V, US)
1 V
1 V
1 V
230 V
460 V
575 V
Defines the nominal motor voltage.
• Must equal the value on the motor rating
plate.
• Sets the maximum drive output voltage
supplied to the motor.
• Drive cannot supply the motor with a
voltage greater than the mains voltage.
9906
MOTOR NOM CURR
0.15*I
2N
… 1.5*I
2N
0.1 A 1.5*I
2N
Defines the nominal motor current.
• Must equal the value on the motor rating plate.
0= ENGLISH 1= ENGLISH (AM) 2= DEUTSCH 3= ITALIANO
4= ESPAÑOL 5= PORTUGUES 6= NEDERLANDS 7= FRANCAIS
8= DANSK 9= SUOMI 10= SVENSKA 11= RUSSKI
12= POLSKI 13= TÜRKCE 14= CZECH 15= MAGYAR
16= ELLINIKA 17= CHINESE 18= KOREAN 19= JAPANESE
1= HVAC DEFAULT 2= SUPPLY FAN 3= RETURN FAN 4= CLNG TWR FAN
5= CONDENSER 6= BOOSTER PUMP 7= PUMP ALTERNA 8= INT TIMER
9= INT TIMER CS 10= FLOATING PNT 11= DUAL SETPPID 12= DL SP PID CS
13= E -BYPASS 14= HAND CONTROL 15= E-CLIPSE 21= AC500 MODBUS
Output voltage
Output
9907
frequency
9905