EasyManuals Logo

ABB ACS320 User Manual

ABB ACS320
442 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #333 background imageLoading...
Page #333 background image
Fieldbus control 333
Max Master Property
Configure the Device Object Max Master property using drive parameter 5313.
Default: 5313 = 127.
MS/TP Token Counter
Parameter 5316 stores the count of MS/TP tokens passed to the associated node.
BACnet protocol implementation conformance statement
This statement is part of this standard and is required for its use.
Date: December 2015
Vendor Name: ABB, Inc
Product Name: Low Voltage AC Motor Drive
Product Model Number: ACS320-xxE (European regional variant)
ACS320-xxU (USA regional variant)
Applications Software Version: 403C (European regional variant)
4050 (USA regional variant)
Firmware Revision: 0528
BACnet Protocol Revision: 7
Product Description: The ACS320 is a high-performance adjustable frequency
drive specifically designed for commercial automation
applications. This product supports native BACnet,
connecting directly to the MS/TP LAN. All standard
MS/TP baud rates are supported, as well as master
mode functionality. Over BACnet, the drive can be fully
controlled as a standard adjustable frequency drive. In
addition, up to 13 configurable I/O ports are available
over BACnet for user application.
BACnet Standardized Device
Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability
Building Blocks Supported
(Annex K):
DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B,
DM-DCC-B, DM-RD-B.
Segmentation Capability: Segmented requests supported. Window Size ____
Segmented responses supported. Window Size ____

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)