Fieldbus control 329
Analog value object instance summary
The following table summarizes the Analog value objects supported:
Instance
ID
Object Name Description Units
Present Value
Access Type
AV0 OUTPUT
SPEED
Indicates motor speed. RPM R
AV1 OUTPUT
FREQ
Indicates output frequency. Hertz R
AV2 DC BUS VOLT Indicates DC bus voltage. Volts R
AV3 OUTPUT VOLT Indicates AC output voltage. Volts R
AV4 CURRENT Indicates output current of the drive. Amps R
AV5 TORQUE Indicates output torque of the motor as
a percentage of nominal torque.
Percent R
AV6 POWER Indicates output power in kW. Kilowatts R
AV7 DRIVE TEMP Indicates heatsink temperature. °C R
AV8 KWH (R) Indicates the resettable energy usage
of the drive (reset by writing zero).
kWh W
AV9 KWH (NR) Indicates the cumulative energy usage
of the drive. The value cannot be reset.
kWh R
AV10 PRC PID FBCK Process PID feedback signal. Percent R
AV11 PRC PID DEV Deviation of the Process PID output
signal from its setpoint.
Percent R
AV12 EXT PID FBCK External PID feedback signal. Percent R
AV13 EXT PID DEV Deviation of External PID output signal
from its setpoint.
Percent R
AV14 RUN TIME (R) Indicates the resettable run time of the
drive (reset by writing zero).
Hours W
AV15 MOTOR TEMP Indicates the motor temperature as set
up in Group 35: Motor temp meas.
°C R
AV16 INPUT REF 1 Sets the input Reference 1 (drive must
be configured for BACnet control).
Percent C
AV17 INPUT REF 2 Sets the input Reference 2 (drive must
be configured for BACnet control).
Percent C
AV18 LAST FLT Indicates most recent fault in the fault
log.
None R
AV19 PREV FLT 1 Indicates previous fault in the fault log. None R
AV20 PREV FLT 2 Indicates the oldest fault in the fault log. None R
AV21 AO 1 ACT Indicates output level of Analog
Output 1.
Milliamps R
AV23 ACCEL1 TIME Sets Ramp1 acceleration time. Seconds W
AV24 DECEL1 TIME Sets Ramp1 deceleration time. Seconds W
AV25 MBOX PARAM Sets the parameter to be used by the
mailbox function. See BV15 and BV16.
None W
AV26 MBOX DATA Sets (W) or indicates (R) as the data
value of mailbox function (see BV15
and BV16).
None W

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)