Planning the electrical installation 39
Additional North American requirements
Type MC continuous corrugated aluminium armor cable with symmetrical grounds or
shielded power cable is recommended for the motor cables if metallic conduit is not
used.
The power cables must be rated for 75 °C (167 °F).
Conduit
Where conduits must be coupled together, bridge the joint with a ground conductor
bonded to the conduit on each side of the joint. Bond the conduits also to the drive
enclosure. Use separate conduits for input power, motor and control wiring. Do not
run motor wiring from more than one drive in the same conduit.
Armored cable / shielded power cable
Six-conductor (three phases and three ground) type MC continuous corrugated
aluminium armor cable with symmetrical grounds is available from the following
suppliers (trade names in parentheses):
Anixter Wire & Cable (Philsheath)
BICC General Corp (Philsheath)
Rockbestos Co. (Gardex)
Oaknite (CLX).
Shielded power cable is available from the following suppliers:
•Belden
LAPPKABEL (ÖLFLEX)
Pirelli.

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)