38 Planning the electrical installation
Alternative power cable types
Power cable types that can be used with the drive are presented below.
Motor cable shield
To function as a protective conductor, the shield must have the same cross-sectional
area as the phase conductors when they are made of the same metal.
To effectively suppress radiated and conducted radio-frequency emissions, the shield
conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminium shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires. The better and tighter the shield, the lower the
emission level and bearing currents.
Symmetrical shielded cable: three phase
conductors, a concentric or otherwise
symmetrically constructed PE conductor
and a shield
Motor cables
(recommended for input cables also)
PE
conductor
and shield
Shield
Shield
PE
PE
Allowed as input cables
A four-conductor system: three phase
conductors and a protective conductor
Note: A separate PE conductor is required
if the conductivity of the cable shield is not
sufficient for the purpose.
Shield
PEPE
Insulation jacket Copper wire screen Cable core

Table of Contents

Other manuals for ABB ACS320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS320 and is the answer not in the manual?

ABB ACS320 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
IP RatingIP20
Frame SizeR1 to R3
Enclosure RatingIP20
Frequency Range0 to 500 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Short circuit, Ground fault, Overtemperature
Fieldbus CommunicationModbus RTU, PROFIBUS DP, CANopen
Communication InterfacesRS485
Operating Temperature-10 to +50 °C (14 to 122 °F)
Storage Temperature-40°C to +70°C
HumidityLess than 95% (non-condensing)
Supply Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)