12-
14
750/760 Feeder Management Relay GE Power Management
12.2 DIRECTIONAL OVERCURRENT CHARACTERISTICS 12 S5 PROTECTION
12
12.2.6 PHASE DIRECTIONAL SETPOINTS
â– PHASE DIRECTIONAL
â– [ENTER] for more
The Phase Directional setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ PHASE CURRENT \ PHASE DIRECTIONAL
PHASE DIRECTIONAL
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
Select the required function.
PHASE DIRECTIONAL
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
PHASE DIRECTIONAL
MTA: 30° LEAD
Range: 0 to 359° in steps of 1
°
Enter the maximum torque angle from 0 to 359°, by which the operating cur-
rent leads the polarizing voltage. This is the angle of maximum sensitivity. The
factory default value for maximum torque angle is 30°. This is an appropriate
angle for an inductive fault angle of 60°, which is typical of the upper voltage
range of distribution feeders. See Figure 12–1: PHASE A DIRECTIONAL
OVERCURRENT POLARIZING on page 12–6 for more information.
MINIMUM POLARIZING
VOLTAGE: 0.05 x VT
Range: 0.00 to 1.25 in steps of 0.01 x VT
BLK OC WHEN VOLT MEM
EXPIRES: Disabled
Range: Disabled, Enabled
Select the required operation upon expiration of voltage memory. When this
setpoint is set to
Enabled
, all phase overcurrent elements under directional
control will be blocked from operating when voltage memory expires. When set
to
Disabled
, all phase overcurrent elements will not be inhibited by directional
control.
This setpoint also determines the operation of the phase overcurrent elements
under directional control upon ‘Close Into Fault’ (CIF).