16-
84
750/760 Feeder Management Relay GE Power Management
16.5 DNP 3.0 DEVICE PROFILE 16 COMMUNICATIONS
16
16.5 DNP 3.0 DEVICE PROFILE 16.5.1 DNP 3.O DEVICE PROFILE DOCUMENT
DNP 3.0
DEVICE PROFILE DOCUMENT
Vendor Name: General Electric Power Mana
ement
Device Name: 750/760 Feeder Mana
ement Relay
Hi
hest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
p
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Hi
hest DNP Levels Supported
(the complete list is described in the attached table):
Binary Input (Object 1, Variations 1 and 2)
Binary Output (Object 10, Variation 2)
Analo
Input (Object 30, Variations 1, 2, 3 and 4)
Analo
Input Chan
e (Object 32, Variations 1, 2, 3 and 4)
Warm Restart (Function code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Application Fra
ment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
p
None
p
Fixed
Confi
urable (Note 1)
Maximum Application Layer Re-tries:
None
p
Confi
urable
Requires Data Link Layer Confirmation:
p
Never
p
Always
p
Sometimes
Confi
urable (Note 1)
Requires Application Layer Confirmation:
p
Never
p
Always
When reportin
Event Data
p
When sendin
multi-fra
ment responses
p
Sometimes
p
Confi
urable
Timeouts while waitin
for:
Data Link Confirm
p
None
p
Fixed
p
Variable Confi
urable (Note 1)
Complete Appl. Fra
ment None
p
Fixed
p
Variable
p
Confi
urable
Application Confirm None
p
Fixed
p
Variable
p
Confi
urable
Complete Appl. Response None
p
Fixed
p
Variable
p
Confi
urable
Others: (None)