EasyManuals Logo
Home>GE>Relays>750

GE 750 User Manual

GE 750
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
6-
6
750/760 Feeder Management Relay GE Power Management
6.2 A1 STATUS 6 ACTUAL VALUES
6
6.2.5 FAULT LOCATIONS
The data for each of ten faults detected by overcurrent elements is stored under headings beginning with
FAULT LOCATION 0. This information cannot be cleared; data for new events is always stored as fault 0. The
data for each previous fault is shifted to the next highest number, and event 9 is discarded.
6.2.6 CLOCK
FAULT LOCATIONS
[ENTER] for more
The Fault Locations actual values path is:
\ ACTUAL VALUES \ A1 STATUS \ FAULT LOCATIONS
FAULT LOCATION 0
[ENTER] FOR MORE
The Fault Location 0 actual values path is:
\ ACTUAL VALUES \ A1 STATUS \ FAULT LOCATION 0
DATE OF FAULT 0
Mar 16 1997
This message displays the date stamp of fault location 0.
TIME OF FAULT 0
12:34:56.789
This message displays the time stamp of fault location 0.
TYPE OF FAULT:
n/a
This message displays the type of fault as determined by the fault locator. The
message is displayed only if a fault location calculation has been performed.
DISTANCE TO FAULT:
0.00 km
This message displays the calculated distance to the fault, as determined by
the fault locator, in the units selected. The message can only be displayed if a
fault location calculation has been performed.
Zpos (INDUCTIVE):
OHM TO FAULT: 0.00
This message displays the calculated impedance from the relay location to the
fault, as determined by the fault locator, in actual Ohms. The message can
only be displayed if a fault location calculation has been performed.
CLOCK
[ENTER] for more
The Clock actual values path is:
\ ACTUAL VALUES \ A1 STATUS \ CLOCK
CURRENT DATE:
November 23 1998
The current date is displayed. If the date has never been programmed, this
message will displayUnavailable”.
CURRENT TIME:
16:30:00
The current time is displayed. If the time has never been programmed, the
message will displayUnavailable”.