13 S6 MONITORING 13.8 EQUIPMENT
13
13.8.6 VT FAILURE
The 750/760 detects a VT fuse failure when there are significant levels of negative sequence voltage without
correspondingly significant levels of negative sequence current measured at the output CTs. Also, if there is
not a significant amount of positive sequence voltage when there is positive sequence current then it could
indicate that all the VT fuses have been pulled or the VTs have been racked out. The setpoints are as follows.
â– VT FAILURE
â– [ENTER] for more
The VT Failure setpoints path is:
\ SETPOINTS \ S6 MONITORING \ EQUIPMENT \ VT FAILURE
VT FAILURE
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
Select the required function.
VT FAILURE
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
VT FAILURE
DELAY: 10 s
Range: 0 to 60000 in steps of 1 s
Select the delay required.