Figure 4-185 Direction for securing cable ties
4.3.2 Cable Routes
General Cable Route
NO TE
When routing cables, leave a distance of at least 100 mm between power cables and signal
cables.
The customer can purchase power cables as required. The recommended
specications of
mains input power cables are as follows:
7.5 kW and 8.5 kW loads (cable BOM code: 25030893): Electronic|Electric Cable,600V/
1000V,ZA-YJV,5x10mm
2
,Black(5Cores:Yellow,Green,Red,Blue,Black),80A,CE
FusionModule800 Smart Small Data Center
User Manual 4 Installation Guide
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 219