Table 5-13 Default alarm thresholds for T/H sensors
Signal Default Value
High temperature alarm threshold 35.0°C
Low temperature alarm threshold 5.0°C
High humidity alarm threshold 85.0% RH
Low humidity alarm threshold 15.0% RH
NTC1–3 high temperature alarm
threshold
35°C
NTC4–6 high temperature alarm
threshold
45°C
NTC1–3 low temperature alarm
threshold
5°C
NTC4–6 low temperature alarm
threshold
10°C
----End
5.3.8.3 Commissioning the WLD900 Water Sensor
If a water sensor is installed, perform the following steps to
congure it.
Prerequisites
One end of the straight-through cable has been connected to the RJ45 port on the
WLDS900 water sensor, and the other end has been connected to the AI/DI_3 port
on the ECC800-Pro.
Context
● To use the AI/DI sensor, enable the corresponding AI/DI port and name the
sensor. The
specic alarm then can be reported.
● If the sensor is prefabricated, only check its settings.
● The actual value prevails. Only the method of the parameter settings is
described.
Procedure
Step 1 Set water sensor parameters.
The default alarm severity of the AI/DI port is Minor. If you want to change the alarm
severity, see How Should I Congure Alarm Parameters.
1. Log in to the ECC800-Pro WebUI as an administrator.
FusionModule800 Smart Small Data Center
User Manual 5 Power-On Commissioning
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 281