NO TICE
When installing temperature sensors, bind the cables behind the sensors to the
cable bridge, keeping them 20 mm away from the sensor probes.
Temperature sensors must not be in touch with metal parts or cabinets.
Keep the temperature sensors facing the inside of the cabinets to ensure
accurate measurement of cabinet interior temperatures.
----End
Follow-up Procedure
Check whether the new temperature sensor works properly. If its status is
displayed on the WebUI of the ECC800-Pro, the new temperature sensor works
properly.
6.4.4.13 Replacing a Smoke Sensor
Prerequisites
Recommended tools and materials: Phillips screwdriver, insulation tape, step
ladder (2 m)
A smoke detector needs to be replaced.
A spare smoke detector of the same model is available and functional.
Context
The smoke detector is installed in the Converged Cabinet, as shown by (1) in
Figure 6-64.
FusionModule800 Smart Small Data Center
User Manual 6 O&M
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 473

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals