1 EU5C-SWD-PF1-1, EU5C-SWD-PF2-1 power modules
1.2 EU5C-SWD-PF1-1
16 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
The subassembly does not need a diagnostics LED and no diagnostics infor-
mation of its own is sent on the SmartWire-DT network. A fault in the 24 V
supply voltage is therefore ascertainable only via the missing voltage of the
downstream contactors.
1.2.2 Engineering
1.2.3 Area of application of the SmartWire-DT power module EU5C-SWD-PF1-1 line AWG24 up to
AWG16
• The supply for the contactors installed in the SmartWire-DT network is no
longer sufficient (power consumption of the contactors > 72 W / 3 A).
• A selective emergency shutdown of individual contactor groups or motor
starter groups is required (→ Chapter 3, „Switching on
DIL-SWD-32-001, DIL-SWD-32-002 contactors“, Page 65).
1.2.4 Installation
The SmartWire-DT power module EU5C-SWD-PF1 is envisaged for mounting
on a top-hat rail.
â–¶ Mount the module on the top hat rail.
â–¶ Connect the 24 V DC voltage to the terminals AUX on the front of the
module.
â–¶ Connect the 8 pole SmartWire-DT cable to the SWD In socket. The con-
tinuation to the next SmartWire-DT module is from the SWD Out socket.
The connection terminals are suitable for cables AWG24 to AWG16 and flex-
ible conductors with a cross section of 0.5 to 1.5 mm
2
.
ï¿«
With a SmartWire-DT power module a second incoming unit for
the contactor coil control voltage can be made at another posi-
tion in the SmartWire-DT network.
ï¿«
For detailed instructions on how to connect the SmartWire-DT
external device plug (SWD4-8SF2-5) to the 8-pin SmartWire-DT
ribbon cable, refer to the "Mount the external device plug" sec-
tion in manual MN05006002Z-EN (previously AWB2723-
1617en).