1 EU5C-SWD-PF1-1, EU5C-SWD-PF2-1 power modules
1.3 EU5C-SWD-PF2-1
20 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
• solid: 0.14 to 1.5 mm²
1.3.4 Cable protection
â–¶ On the SmartWire-DT gateway connect the POW and AUX supply volt-
ages via separate miniature circuit-breakers or fuses:
• Miniature circuit-breaker 24 V DC for POW
• Cable protection in accordance with DIN VDE 0641 Part 11,
IEC/EN 60898:
• Miniature circuit-breaker 24 V DC rated operational current 3 A;
trip type C or
• Fuse 3 A, utilization category gL/gG
• Cable protection for cable AWG24 in accordance with UL 508 and
CSA-22.2 no. 14:
• Miniature circuit-breaker 24 V DC rated operational current 2 A;
tripping characteristics C or
• Fuse 2 A
• Miniature circuit-breaker 24 V DC for AUX
• Cable protection in accordance with DIN VDE 0641 Part 11,
IEC/EN 60898:
• Miniature circuit-breaker 24 V DC rated operational current 3 A;
trip type Z or
• Fuse 3 A, utilization category gL/gG
• Cable protection for cable AWG24 in accordance with UL 508 and
CSA-22.2 no. 14:
• Miniature circuit-breaker 24 V DC rated operational current 2 A;
tripping characteristics Z or
• Fuse 2 A
1.3.5 Diagnostics
The device does not report a diagnosis