4 PKE-SWD-32, interface for motor-starter combination with PKE PKE12/32
4.3 Engineering
SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 87
The PKE-SWD-32 is set to the respective contactor size via the slide adjuster
for the contactor size . This enables the module to be set to size 1 (DILM7
to DILM15) contactors and size 2 (DILM17 to DILM32) contactors.
The PKE32-COM is used as a communication link between the PKE-SWD-32
and the PKE-XTUA-… trip block. The data is exchanged via the data interface
of the PKE trip block and the data interface on the PKE-SWD-32. The
PKE32-COM module is used for transferring the signals. This connects the
data interfaces of the PKE trip block and the PKE-SWD-32.The PKE-SWD-32
receives the data of the PKE trip block and makes this available on the Smart-
Wire-DT network.
The 1-0-A selector switch is used to manually make an electrical activation
of the connected contactor as required.
4.3 Engineering
The PKE-SWD-32 can be combined with DILM7 to DILM32 contactors in
conjunction with the PKE12 and PKE32 electronic motor protective circuit
breaker and the “Advanced” part no. (PKE-XTUA-…) trip blocks. The DILM7
to 32, PKE12 / PKE32 components and the PKE-XTUA-… trip block are avail-
able likewise as networkable motor starter combinations (MSC-DEA-…), and
can also be combined with the PKE-SWD-32.
Each PKE-SWD-32 can be connected to a DILM7 to DILM32 contactor and a
PKE12 to PKE32 with a PKE-XTUA-... trip block. With reversing starters con-
sisting of two contactors and one PKE electronic motor protective circuit
breaker, the actuation of the second contactor can be implemented with the
DIL-SWD-32-001 or DIL-SWD-32-002 SmartWire-DT contactor modules
( Chapter 3, "Switching on DIL-SWD-32-001, DIL-SWD-32-002 contactors",
page 65).
Table 7: Combination options
The connected contactor is fed directly via the SmartWire-DT connection
cable. The contactor coils have the following power consumptions with a
voltage of 24 V DC:
Application Number of
PKE-SWD-32
Number of
DIL-SWD-32
Electronic motor starter MSC-DEA
DOL starter (PKE and DILM) 1 0
Reversing starter (PKE and 2 x DILM)
1 1