Menus 15 to 17
SM-I/O PELV
Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
304 Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
5.17.6 SM-IO PELV
Table 5-18 Solutions Module error status values for SM-IO PELV
Figure 5-19 SM-I/O PELV digital I/O logic diagram
Error code Fault description
0 No errors
1 Digital outputs overloaded
2 Digital inputs overloaded
3 Analog input trip (4-20.tr/20-4.tr). (Occurs when input is <3.0mA).
4 PELV user power supply absent
74 Solutions Module over temperature (>100°C)
T3 digital
I/O 1 state
X.31
T3 digital I/O
1 output select
Any bit or
integer
parameter
X.21
T3 digital I/O
1 source/
destination
x(-1)
x(-1)
X.11
T3 digital
I/O 1 invert
X.09
(RW)
parameter
Read-only (RO)
parameter
Input
terminals
Output
terminals
The parameters are all shown at their default setting
X.32
X.22
x(-1)
x(-1)
X.12
X.10
T4 digital I/O 2
T4 digital
I/O 2 state
T4 digital I/O
2 output select
T4 digital I/O
2 source/
destination
T4 digital
I/O 2 invert
Any
unprotected
bit parameter
Any bit or
integer
parameter
X.33
x(-1)
x(-1)
X.13
X.03
T5 digital I/O 3
T5 digital
I/O 3 state
T5 digital I/O
3 output select
T5 digital I/O
3 source/
destination
T5 digital
I/O 3 invert
Any
unprotected
bit parameter
Any bit or
integer
parameter
T6 digital
I/O 4 state
T6 digital I/O
4 output select
T6 digital I/O
4 source/
destination
T6 digital
I/O 4 invert
Any
unprotected
bit parameter
Any bit or
integer
parameter