Flux controller (ASM)
The flux controller for the asynchronous motor is a PI controller.
The set flow (ImrRef) is made up of a characteristic value (flux control) and the out-
put of the maximum voltage controller.
Different options for the flux controller can be selected with fc16 ASM flux mode.
Flux controller off (limit = 0)
Flux controller limits constant = fc20
cubic => Flux controller limit rises cubically (x³) from 0 at speed
0 to fc20 at speed dr25 (breakdown speed)
start off => the flux controller is not active at flux build-up
start on => the flux controller limit fc20 applies at flux build-up
on => the flux build-up is await for starting normal operation
(e.g. transfer of speed setpoints). The drive remains in the
"Start operation active" status during the waiting time
Flux in % of the rated flow, when the magnetization is consid-
ered as completed
Flux controller-total gain
Flux controller limit in % of the rated motor current (dr03)
Figure 80: Flux controller (ASM)
I
sdRef
-
fc18
Flux
controller
I
mrAct
fc19
fc20 fc16
I
mrRef
FluxCurve
I
mrRefN
Uic
Act
Tr/25
frequency