Digital Inputs
© 2022 KEB Automation KG
425
The meaning of the single bits in ru18 dig. input state is defined as follows:
ru18
dig. input state
0x2C12
Value
Bit
Name
Function
1
0
I1
Input state I1
2
1
I2
Input state I2
4
2
I3
Input state I3
8
3
I4
Input state I4
16
4
I5
Input state I5
32
5
I6
Input state I6
64
6
I7
Input state I7
128
7
I8
Input state I8
256
8
IA
Input state IA
512
9
IB
Input state IB
1024
10
IC
Input state IC
2048
11
ID
Input state ID (can only be set by the input block)
4096
12
CW 1
Controlword input 1
8192
13
CW 2
Controlword input 2
16384
14
STO-1
Channel 1 from the safety mod-
ule
Can not be changed by the input
block
32768
15
STO-2
Channel 2 from the safety mod-
ule
1 means that the state of the input is set to active at the output of the processing
block of the digital inputs.
Selection of the input source
The source for the internal terminal state can be selected via the object di01 dig.
input src. sel.
Index
Id-Text
Name
Function
0x3201
di01
dig. input src. sel.
Selection of the internal terminal state source
It can be selected from the 4 sources below for inputs I1...I8 and IA...ID.
The terminal block is always used as source for inputs STO-1 and STO-2.
The selection of the source is done for each input via 2 successive bits in di01 dig.
input src. sel. The meaning of this source selection is identical for each input.

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals