Motor parameterization
358
© 2022 KEB Automation KG
is02
Uic comp voltage limit
0x3502
Value
Meaning
10V…800V
Maximum output voltage (effective value)
Identification
6.2.18.1 Function
Motor parameters, which are not specified on the type plate or in the data sheet
can be determined with the identification.
The dead-time characteristic of the inverter can be determined additionally.
Condition for starting the identification is the correct input of the motor type and
rated current, rated voltage, rated speed and rated frequency.
Presettings for the controller and limitations for the test signals are determined
from this data.
Also the encoder parameters (type, increments, etc.) must be preset at speed con-
trol with encoder.
The identification determines the following motor data:
Asynchronous machine
Index
Id-Text
Name
Function
0x2211
dr17
stator resistance UV
Stator resistance in Ohm
0x2212
dr18
ASM rotor resist. UV %
Rotor resistance in % of the stator resistance
0x2213
dr19
ASM head inductance UV
Head inductance
0x2215
dr21
ASM sigma stator ind. UV
Stator leakage inductance in mH
0x2216
dr22
ASM sigma rotor ind. %
Rotor leakage inductance in % of the stator value
Synchronous machine
Index
Id-Text
Name
Function
0x220E
dr14
SM EMF [Vpk/(1000min-
1)]
EMC (peak value of the phase-to-phase voltage) at
1000 rpm in V
0x220F
dr15
SM inductance q-axis UV
Cross inductance (inductance q-axis) in mH
0x2210
dr16
SM inductance d-axis %
Series inductance (inductance d-axis) in % of dr15.
0x2211
dr17
stator resistance UV
Stator resistance in Ohm
Inverter
Index
Id-Text
Name
Function
0x3506
is06
deadtime coeff
Deadtime characteristic
Either all or only single motor parameters can be identified.
The automatic mode (mode 1 or 2 "all") is the simplest method of parameter identi-
fication.
Single identifications should not be used for the first measurement of the motor pa-
rameters, since wrong measurement results can occur with wrong identification or-
der or missing of single points.
The single identification can always be used if a complete automatic measurement
has been executed and only single parameters should be identified new. This can

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals