6.2.16.3 Model stabilization
6.2.16.3.1 Stabilisation current / standstill current (only SCL)
The stabilisation current stabilises the model at lower speeds. Only active for oper-
ation without encoder.
It is reduced to zero in the speed range of ds36 to ds37.
➢ Note for synchronous reluctance motor: From version V2.9, ds35 also serves
as stabilisation current for the synchronous reluctance motors. Parameters
ds36 and ds37 have no effect. The stabilisation current is permanently neces-
sary, independent of the speed.
scl stabilisation
current
Activates / deactivates the stabilisation current in en-
coderless operation (SCL)
The stabilisation current characteristic is parameterized with ds35…ds37.
scl stabilisation current
Stabilisation current in % of the rated motor current.
Only for the synchronous machine it can be useful to
specify a negative stabilisation current.
min. speed for stab. cur-
rent
Speed limits (in % rated motor speed), which lowering
the stabilisation current to 0 (value programmed in
ds35)
max. speed for stab. cur-
rent
50% rated motor current
5% rated speed
10% rated speed
Figure 91: Stabilisation current depending on speed
stabilisation current [% dr03]
actual speed [% dr04]