Figure 84: v/f – Influence of the DC link voltage compensation
All voltage values of the blue characteristic are increased compared to the charac-
teristic with DC link voltage compensation by the factor real DC link voltage to
rated DC link voltage: ru14 Uic voltage / rated DC link voltage = 620V / 565V = 1.1
Voltage at 50Hz in graphic: 362V to 330V = 1.1
6.2.15.1.6.3 Influence of the maximum degree of modulation