Motor parameterization
© 2022 KEB Automation KG
367
Deadtime compensation
6.2.19.1 General modification
A distortion of the output voltage occurs by the deadtimes of the power modules,
which causes negative effects (e.g.) for the calculation of the motor model or in
voltage-frequency-characteristic operation. This distortion can be compensated
partly by the activation of the deadtime compensation.
NOTICE
The dead time compensation has been generally revised in the software 2.10 /
3.0.
Instead of the previous dead time compensation based on an e-function, an
IGBT model is now used.
The values identified with the e-function compensation (is05, is06 or
is40...is43 deadtime coeff fswx) can no longer be used.
The compensation was deactivated by default in all previous software versions.
Now the compensation is activated on the basis of the IGBT model calibrated
in the factory, independent of the control mode (also in v/f mode).
For is07 deadtime comp mode value "2: ident“ is no longer allowed. Attempt-
ing to write this value results in the error message "Data invalid".
Value "1: e-function“ is still possible for is07 for compatibility with already ex-
isting applications. Then the dead time compensation continues with the e-
function compensation values calibrated at the factory.
Parameters is05, is06 and is40...is43 are internally available for download
compatibility reasons, but they have no function and they are not visible in
COMBIVIS.
Index
Id-Text
Name
Function
0x3503
is03
deadtime switch on/off
Enables speed-dependent activation/deactivation of the
dead time compensation. Setting of the speed level in %
dr04 rated speed.
0x3504
is04
deadtime IGTB model
Evaluation/parameterization of the IGBT model.
0x3507
is07
deadtime comp mode
Selection of the compensation mode
0x3508
is08
comp limit fact
Adjustment of the dead time characteristic (only for e-func-
tion)
Values should always be set to 100%
0x3509
is09
comp current fact

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals