AN1 interface selection / AN2 interface selection
7.3.2.2 Interface monitoring (not available for compact cards)
Only the 4...20mA interface can be monitored for line breakage.
All measured values are valid for the two remaining interface types, thus no line breakage
can be detected.
Furthermore, a line breakage at the +/- 10V interface does not lead to a 0% input signal,
because an undefined differential signal can be generated.
Stop mode selection (see description and notes about the stop modes
at 4.3.1.2.2 Error reaction)
Upper limit of this parameter is 8.
It is not advisable to use a stop mode that enables a restart, since un-
defined behavior can occur if the contact is faulty ("loose contact").
Error is triggered independently of the modulation
Error is only triggered when the modulation is switched on.
The warning bit is always set.
This setting must never be combined with "Auto-Retry",
otherwise there will be a permanent change of restart and
error triggering.
Input level of the analog inputs
Mean filter for the analog signal.
PT1 filter for the analog input
AN1 zero point hysteresis
AN2 zero point hysteresis
Gain of the analog signal
Offset X for the analog signal
Offset y for the analog signal
Out = gain * (In – OffsetX) + OffsetY