Figure 87: Model deactivation depending on the motor type
6.2.16.1.3 Model deactivation (bit0...2) and (bit3...5) = always on
The model is active after magnetisation and remains, independent of the set / ac-
tual speed.
6.2.16.1.4 Model deactivation ds41 (Bit 0…2) and (Bit 3…5) = „dep. on act. speed“
The model activation occurs if the actual value is above the model activation
threshold
(= model deactivation threshold ds46 hysterese ds47).
The model deactivation occurs when the actual value is below the model deacti-
vation threshold (ds46).
With deactivation of the model in encoderless operation ((A)SCL) it is switchted to
the model replacement („low speed ctrl“ ds41 Bit 8…9).