Connection to the file system
512
© 2022 KEB Automation KG
10.5 Connection to the file system
The drive controller has a file system to store the recipe (download) files.
COMBIVIS 6 contains the program KEB FTP, which allows access to these files via the
diagnostic interface. => See also the help contained in COMBIVIS 6.
The used interface adapter must support a direct connection.
i
Connection directly to serial D-SUB 9-pole protocol DIN 66019 II: RS-232 ca-
ble PC / operator / Part No. 0058025-001D
KEB USB serial converter - use only if the nameplate contains the imprint
FTP Ready, otherwise KEB FTP does not work.
FTP connection set-up
Open KEB FTP and make the following settings. Do not press CONNECT yet!
Enter the used interface in COM.
With KEB FTP only 115200 baud are possible in conjunction with the drive controller,
other settings do not work.
2
1
1fghfh
1
Figure 136: Set the baud rate
Set de10 operator cfg data SubIdx 9 com mode to 1 to activate the FTP protocol with
115200 baud in the drive controller. FTP access is only possible if the drive does not
modulate. Otherwise, the write access to this object is acknowledged negatively.
Then quickly disconnect the connection to the inverter in the communication settings.

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals