EasyManuals Logo
Home>KEB>Controller>COMBIVERT F6

KEB COMBIVERT F6 Programming Manual

KEB COMBIVERT F6
544 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #55 background imageLoading...
Page #55 background image
Protection functions
© 2022 KEB Automation KG
55
The following diagram shows the switch-off time for an inverter with overload char-
acteristics depending on the constant load:
OL- trigger time:
actual current:
inverter rated current:
OL-tripping time at constant load
Motor current
Inverter rated current
21
1fghfh
1
Figure 6: Overload characteristic
The overload characteristic valid for the respective inverter can be found in the in-
stallation manual for the power unit.
The drive switches off automatically on reaching the overload limit (ru29 OL coun-
ter = 100%).
The error reaction can be programmed as described above via the object pn04
E.OL stop mode . A warning level can be programmed additionally.
On reaching this "OL-Counter“ value bit 0 is set in the warning state and with ap-
propriate adjustment of the warning mask also bit 7 is set in the status word.
The error or warning can be reset when the OL counter has reached the value of *
pn03 OL warning level / 2.

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals