Ramp state ACC or CONST:
If the apparent current is higher than the maximum current, the current control-
ler intervenes. The current controller (ds00…ds03) is parameterized via the
equivalent circuit data (dr17, dr18, dr21 and dr22) of the motor. The default val-
ues for the equivalent circuit data can be calculated from the nameplate data
with dr99 motor data control = 2. Better results for the current controller param-
eterization are achieved with the motor identification.
Ramp state DEC:
If the apparent current is higher than the maximum current, the modulation is
switched off for one current measurement cycle.
The speed setpoint ramp is decelerated / stopped dur-
ing deceleration (DEC) if the apparent current >
Imax
(*1)
or the rate of current rise is too high.
The speed setpoint ramp is decelerated / stopped dur-
ing deceleration (DEC) if the DC link voltage > ds60[3]
LD-U stop level or the rate of voltage rise is too high.
The speed setpoint ramp is decelerated / stopped dur-
ing acceleration (ACC) if the apparent current >
Imax
(*1)
or the rate of current rise is too high.
(*1)
The maximum current "Imax" is formed from the following parameters: dr12
max. current %, is11 max current [de28%], is14 overload protect mode