Motor parameterization
© 2022 KEB Automation KG
391
ds62
DC braking mode
0x243E Sub Idx. 1
Bit
Function
Value
Plaintext
Notes
12,13
start af-
ter
switched
on
0
off
No DC braking at the start
4096
on
The DC braking is activated at the change from st12 state
machine display 4: switched on to 11: start operation activ
6.2.26.3.1 DC braking: mode (Bit 0…2)
Currently, only one DC braking mode is implemented:
Switching off the modulation for a preset time / reduction of the magnetic
flux
Connecting a DC voltage vector for a parameterizable time
6.2.26.3.2 DC braking: start by digital input sel (Bit 3…5)
An activation condition is the start by digital input (Bit 3: start by digital input selec-
tion = "8: on“ or "16: on + speed level“)
An activation input must be selected in ds61 DC braking source:
ds61
DC braking source
0x243D
Bit
Value
Name
Start by
0…15
0
no in-
put
Function off
0
1
I1
Input I1
1
2
I2
Input I2
2
4
I3
Input I3
3
8
I4
Input I4
4
16
I5
Input I5
5
32
I6
Input I6
6
64
I7
Input I7
7
128
I8
Input I8
8
256
IA
Input IA
9
512
IB
Input IB
10
1024
IC
Input IC
11
2048
ID
Input ID
12…15
reserved
With “start by digital input selection = 16: on + speed level“ the requested actual
speed level must additionally be set in ds62[7] braking speed level [%Nn].
6.2.26.3.3 DC braking: start in stopping state (Bit 6…8)
Start of the DC braking in state: “quickstop“, “fault reaction“, “shut down“, “disable
operation active”. During operation in the torque limit, the speed setpoint at the
ramp output can reach zero before the actual speed has fallen below ds62[7] brak-
ing speed level [%Nn].
To ensure that the DC braking is safely activated with the setting 128: on + speed
level, the waiting time before the modulation switch-off (pn45 fault reaction time)
must be configured accordingly.

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals