AMT/PTD/PBX/0058/4/6/EN Installation and Maintenance Manual - Aastra 5000
Page 320 01/2011 Installation and activation
6.2.4.1 Powering on the system
Before switching on the power, check that:
• The cabinet is permanently connected to the ground socket
• Air flows freely all around the cabinet(s) and there are no objects lying on the cabinet.
There must be sufficient space between the cabinet and the wall.
• All expansion cards are connected (AXD, AXL, AXS, AXS12 and AXS6 cabinets).
• All equipment is connected to the cabinet and grounded.
If an external 48 V battery (AXL, AXS, AXS12 and AXS6 cabinet option) is used, check its
connection to the power module or at the back of the AXD cabinet.
For a system with only 1 cabinet
• Set the “I/O” push button to “I”.
For a system with only several cabinets
In systems with 2 or 3 cabinets, first power on the expansion cabinet(s) (“I/O” push-button
in position “I”) then the main cabinet.
6.2.4.2 Viewing the status of the indicators located on the CPU card(s)
Refer to Chapter 4 for each type of configuration.
6.2.5 Starting up a new system
Since the system has been pre-set in the factory, to start it up, you only need to define the IP
parameters on the CPU card.
Access is provided locally on the COM port of the CPU card, using a NULL MODEM cable (ref.:
:BHG0024A) connected between the COM port of the CPU card and the PC COM port.
Procedure
On the PC connected to the COM port
• Open a Hyperterminal window and configure the connection as follows:
- Bits per second: 115200 bits/s
- Data bits: 8
- Parity: none
- Stop bits: 1
- Flow control: None
• Power on the cabinet and follow the start-up progress on the PC:
• Upon display of "Identification starting"
•Press Ctrl + I