5.3 Transporting the components
Ambient and operating conditions for transport
Description Symbol Unit Value
Temperature range T
a_tran
°C -20 … +70
Relative humidity % 5 … 95
Absolute humidity
g/m
3
1 … 60
Climatic category (IEC 721) 2K3
Moisture condensation Not allowed
Icing Not allowed
Tab. 5-3: Ambient and operating conditions for transport
5.4 Storing the components
Risk of damage to components from long-
term storage!
Some components contain electrolytic capacitors which may deteriorate dur‐
ing storage.
When storing the following components for a longer period of time, run them
once a year for at least 1 hour:
● Converters and supply units: Operated with mains voltage U
LN
● Inverters and DC bus capacitor units: Operated with DC bus voltage
U
DC
Ambient and operating conditions for storage
Description Symbol Unit Value
Temperature range T
a_store
°C -20 … +55
Relative humidity % 5 … 95
Absolute humidity
g/m
3
1 … 29
Climatic category (IEC 721) 1K3
Moisture condensation Not allowed
Icing Not allowed
Tab. 5-4: Ambient and operating conditions for storage
Bosch Rexroth AG DOK-INDRV*-HCS01******-PR05-EN-P120/341
Rexroth IndraDrive CsDrive Systems with HCS01
Condition as supplied, identification, transport and storage