Selection of the step size limitation in jog mode.
The setpoint is enabled as long as the preset step
distance has not been exceeded.
4.8.8.1.1 Error handling in jog mode
By activating the jog mode via the digital input specified in cm34, any errors that
may have occurred are automatically reset once. The two fieldbus errors from pn22
E.fb watchdog and pn23 E.fb heartbeat are not active in jog mode. Hardware limit
switches and software limit positions are observed in jog mode, errors which are
selectable by pn20 E.SW-switch stop mode, pn78 limit swich forware stop mode
and pn79 limit switch reverse stop mode are suppressed.
4.8.8.1.2 Status machine in jog mode
If the jog mode is activated via co01 modes of operation, the status machine is not
affected. This must be started via the co00 (CiA 0x6040) controlword.
If the input function is used with cm34, the status machine is first briefly reset, then
after an error reset the status machine is automatically started up to Operation En-
abled. For this the co00 (CiA 0x6040) controlword is internally switched off. If the
input of cm34 is deactivated again, the status machine is shut down again. The
drive cannot start unintentionally when leaving the jog mode.
4.8.8.1.3 Setpoints
Definition of setpoints in jog mode: