6.2.3.4 Motor protection
Index
Id-Text
Name
Function
0x2221
dr33
motor temp sensor type
0 = KTY 84-130, 1 = PTC, 2 = via encoder, 3 = KTY
83 110, 4 = PT1000
0x2222
dr34
motor protection curr. %
Standstill current (permanent permissible current at
standstill) in % of rated motor current
0x2203
dr03
rated current
Rated current = permanent permissible current at
rated speed
0x2226
dr38
SM prot min. Is/Id
Application point of the motor protection function in
% of the permanent permissible current
0x220C
dr12
max. current %
Max. current in % rated motor current
0x2223
dr35
SM prot time min. Is/Id
Time, after the protection function is triggered at
min. current flow (defined dr38)
0x2224
dr36
SM prot. time Imax
Time, after the protection function is triggered at
max. current flow (defined dr12)
0x2225
dr37
SM prot. recovery time
The prot. recovery time is the time, which the pro-
tection function counter needs to count from 100%
to 0%.
The overtemperature motor protection is parameterized with this objects (=> Chap-
ter 4.4.5 Overtemperature motor (dOH) and chapter 4.4.6 Motor protection switch
OH2 ).

Table of Contents

Other manuals for KEB COMBIVERT F6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F6 and is the answer not in the manual?

KEB COMBIVERT F6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F6
CategoryController
LanguageEnglish

Related product manuals