7.3.6.5 Reset conditions
The PID controller or only the I-component of the PID controller can be reset depending
on the state machine status but also depending on digital inputs.
The value to which the I-component is reset in this case can be parameterized.
By means of an adjustable fade-out time, the controller output value can be lowered on
reset via an adjustable linear function or increased linearly at start-up.
Object an69 PID internal reset condition defines the conditions and how the PID controller
shall be reset.
PID internal reset condition
Reset conditions for the PID controller
PID internal reset condition
All values of st12 state machine
display can be selected as reset
condition for the PID controller.
Reset is preset when not in status
"operation enabled".
quick stop reaction active
Selection how to reset the PID pro-
cess controller. The I-part is set to
the value of an72 PID preload
value.
Selection how the fade out func-
tion shall be initialized.