14.10.16 Select unit
During batch control, you have the option of selecting a new unit, for example, after aborting
a unit with this command. This function can only be used for recipe elements that can be
configured with an allocation strategy.
14.10.17 Release unit
During batch control, you have the option of aborting the units involved. This function can be
used on the elements RP, RUP, ROP, RPH and Transition that have a unique assignment to
a unit allocated by SIMATIC BATCH.
In a flat recipe, this command is used to abort all recipe phases allocated to this unit before
the unit is aborted.
Removes a set breakpoint in the open control recipe for a control recipe element. The control
recipe element must have been selected beforehand.
14.10.18 Reset unit
During batch control, you have the option of resetting the affected unit. This function can be
used on the elements RP, RUP, ROP, RPH and Transition that have a unique assignment to
a unit used by SIMATIC BATCH.
This command caused all recipe phases in a flat recipe used in this unit to be reset before the
unit is reset.
14.10.19 Open overview
Function
This function opens an overview window of the SFC visualization. Double-click in the window
to display the content. The overview window is not closed automatically not even when
BatchCC is closed. If you open the overview window again in another BatchCC, the overview
window can be displayed twice.
If the "Always display in faceplate" check box is enabled in the SFC topology settings in the
WinCC Explorer, the SFC visualization is always displayed with the SFC overview window and
SFC detail window.
Requirements
● The corresponding recipe phase must be configured as an SFC type in PCS 7 Engineering.
● The PCS 7 OS Client add-on must also be installed on the PC in addition to an installation
of the BATCH Client.
Context help references
14.10 Shortcut menu commands
SIMATIC BATCH V8.2
1120 Operating Manual, 02/2016, A5E35958174-AA