WARNING
Operator responsibility
As the operator you are responsible for leaving an active batch in a secure state before
transferring the batch to OSC processing mode.
9.8.8.2 Scope of services and features
Scope of services
Online changes to the recipe structure are available for both flat and hierarchical recipes.
The master recipes used in batches must have the status "Release for testing".
The control recipe must be open in the window of BatchCC and the window must be active.
Online structure changes are adopted independent of the block version.
All commands available for the online structure change can be found in BatchCC in the
"Control" menu. The commands for inserting new recipe elements (RUP, ROP, RPH, loop,
synchronization, etc.) are set via the BatchCC toolbar activated when starting OSC mode.
In the "Batches" folder of the project settings, you can select or clear the "Active batches
have to be held" option. Selecting the option means that the batch must be paused for the
online structure change. When the option is deselected, the batch and thus the process
continue running in AS.
The right "start structure changes" was introduced for the online structure change.
Features
Other clients are not permitted access to a batch in OSC mode and the BatchCC prevents
the process editing of this batch.
All the usual editing functions are available.
You can exit the "OSC processing mode" in two ways:
Accepting changes: By selecting the command "Accept changes", the altered control
recipe is validated. If no errors occur during the check, changes are transferred to the
current batch and OSC processing mode is stopped.
Rejecting changes: All changes made are rejected.
As soon as changes have been saved to a batch or rejected, the batch can be resumed
either at the point at which it was paused or at any other point in the control recipe.
BATCH Control Center
9.8 Batch control
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA 459

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC BATCH and is the answer not in the manual?

Siemens SIMATIC BATCH Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC BATCH
CategoryControl Systems
LanguageEnglish

Related product manuals