12.For the Windows Server and Windows 7 operating systems, the BATCH Control server
must be modified in such a way that it is started as an interactive user and not by the launch
coordinator in system mode.
To do this, open the "Properties of Bfserverhostx" dialog by selecting Start > Run and
specifying "dcomcnfg".
Select the DCOM configuration "Bfserverhostx".
Click on "Properties" in the shortcut menu.
Change to the "Identity" tab.
Select the "Interactive user" option.
Close the dialog with "OK".
13.Restart your PC.
14.Open the "Services" dialog via Start> Run specifying "services.msc".
15.Start the "SIMATIC BATCH Server Control Service".
This step is required after every restart of the PC.
16.After BATCH Runtime starts again, start BatchCC.
17.Update the process cell to adopt the data.
18.Create a new batch that uses a control recipe in which recipe unit procedures are executed
in the AS.
19.Release the batch.
20.Start the batch for simulation.
Result
They have simulated your user program in S7-PLCSIM.
12.8 How do I configure and use dynamic unit parameters?
12.8.1 How do I configure parameter steps?
A parameter step refers to a recipe step in a master recipe at which parameter values are
configured that are passed to a unit. During configuration in the Recipe Editor, the parameter
step is identified by a special symbol, a frame at the recipe step symbol. In this example, you
pass setpoints to a unit that you then query in a transition condition. To control the properties
of units using batch control, some configurations in components from basic engineering and
BATCH engineering are required.
Requirements
The software and the project have been updated.
You are using BATCH blocks from the current block library.
Recommended procedure
12.8 How do I configure and use dynamic unit parameters?
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA 689

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC BATCH and is the answer not in the manual?

Siemens SIMATIC BATCH Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC BATCH
CategoryControl Systems
LanguageEnglish

Related product manuals