Image 9-22 Continue, cancel, stop SFC
Operating the BATCH batch: It is your responsibility as the user to decide when to continue,
cancel or stop an interrupted batch after manual operation. Continuation of the batch can also
be made at a later step.
Online Help: SFC :for SIMATIC S7
Additional information is contained in the online help: SFC :for SIMATIC S7, topic: Processing
an SFC after a CPU stop and restart
9.8.5.18 Operation of batches after restart of CPU, SFC and batch interface blocks
Batch operation after CPU restart using SFC plan and BATCH interface block
A CPU stop and subsequent restart generates an error with a running batch which interrupts
this batch. To continue, cancel or stop, the batch must be manually operated.
In SIMATIC BATCH, there are two configuration possibilities. The following describes the
procedure when using SFC plan and BATCH interface block