9.6.2.9 Displaying formula parameters and modifying them if necessary
Changing a formula
In the properties dialog for the batch, you can make the final modifications to the formula
parameters.
Note
Formula parameters modified at this point apply only to this batch. The parameter values are
not changed in the formula used or in the master recipe used in the tree of BatchCC.
Procedure in the BatchCC:
1. In the "Orders" folder in the BatchCC select the object "Batch" below the production order.
2. Select the menu item Edit > Properties.
Result: The dialog "Properties of <batch name>" is displayed.
3. Change to the "Input material", "Output material", or "Parameters" tab.
Result: Tables are opened displaying all the header parameters of the master recipe with
the current values of the formula parameters.
4. If required, change the values of the formula parameters. The possible range of values are
displayed as the upper and lower limits.
5. Confirm changes with "OK".
9.6.2.10 Displaying the chaining of a batch
In the properties dialog of a charge, you can display any chaining of the batch and set and
change the start mode.
Procedure in the BatchCC:
1. In the "Orders" folder in the BatchCC select the object "Batch" below the production order.
2. Select the menu item Edit > Properties.
Result: The dialog "Properties of <batch name>" is displayed.
3. Select the "Chaining" tab.
Result: The defined predecessor/successors are displayed in the table.
4. If necessary, modify the chaining.
5. Confirm changes with "OK".
9.6.2.11 Scheduling batches; chaining batches
If you want to make sure that a batch is only started after a previous batch has been completed,
you can also chain planned and not yet released batches. You can specify a predecessor
batch and then specify whether the predecessor batch is to be started or already completed.
BATCH Control Center
9.6 Batch Planning
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA 359

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC BATCH and is the answer not in the manual?

Siemens SIMATIC BATCH Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC BATCH
CategoryControl Systems
LanguageEnglish

Related product manuals