10.4 Selecting a Motor Drive Control
10-19
Chapter 10 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES
10.4 Selecting a Motor Drive Control
10.4.1 Features of motor drive controls
The FRENIC-MEGA supports the following motor drive controls.
This section shows their basic configurations and describes their features.
Table 10.4-1
Drive control
Basic
control
Speed
feedback
Drive control
class
Speed control Other restrictions
V/f control with slip
compensation inactive
Frequency control ―
Dynamic torque vector
control
―
V/f control with slip
compensation active
Disable V/f
Frequency control
with slip
compensation
―
V/f control with speed
sensor
*
Dynamic torque vector
control with speed
sensor
*
V/f
control
Enable PG V/f
Frequency control
with automatic
speed regulator
(ASR)
Maximum
frequency: 200 Hz
Vector control
without speed sensor
Estimated
speed
w/o PG
Maximum
frequency: 120 Hz
Not available for
MD-mode
inverters.
Vector control
with speed sensor
*
Vector
control
Enable w/ PG
Speed control
with automatic
speed regulator
(ASR)
Maximum
frequency: 200 Hz
Note that the controls marked with an asterisk (
*
) require an optional PG (Pulse Generator)
interface card.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fuji Electric Frenic Mega Series and is the answer not in the manual?

Fuji Electric Frenic Mega Series Specifications

General IconGeneral
BrandFuji Electric
ModelFrenic Mega Series
CategoryInverter
LanguageEnglish

Related product manuals