12.1 Standard Model 1 (Basic Type)
12-1
Chapter 12 SPECIFICATIONS
12.1 Standard Model 1 (Basic Type)
12.1.1 Three-phase 200 V class series
HD (High Duty)-mode inverters for heavy load
Item Specifications
Type (FRN***G1S-2J) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Nominal applied motor
(kW)
*1
(Output rating)
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Rated capacity (kVA)
*2
1.1 1.9 3.0 4.2 6.8 10 14 18 24 28 34 45 55 68 81 107 131
Rated voltage (V)
*3
Three-phase 200 to 240 V (with AVR function) Three-phase 200 to 230 V (with AVR function)
Rated current (A) 3 5 8 11 18 27 37 49 63 76 90 119 146 180 215 283 346
Output ratings
Overload capability 150%-1 min, 200%-3.0 s
Voltage, frequency 200 to 240 V, 50/60 Hz
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5
, Frequency: +5 to -5%
Input power
Required capacity
(with DCR) (kVA)
*6
0.6 1.2 2.2 3.1 5.2 7.4 10 15 20 25 30 40 48 58 71 98 116
Torque (%)
*7
150% 100% 20% 10 to 15%
Braking transistor Built-in
Built-in braking resistor
Braking time (s)
5 s
Braking
Duty cycle (%ED) 5 3 5 3 2 3 2
DC reactor (DCR)
*8
Option
Provided as
standard
Applicable safety
standards
UL508C, C22.2 No.14, IEC/EN61800-5-1:2007
Enclosure (IEC60529) IP20, UL enclosed type IP00, UL open type
Cooling method Natural cooling Fan cooling
Weight / Mass (kg) 1.7 2.0 2.8 3.0 3.0 6.5 6.5 5.8 9.5 9.5 10 25 32 42 43 62 105
LD (Low Duty)-mode inverters for light load
Item Specifications
Type (FRN***G1S-2J) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Nominal applied motor
(kW)
*1
(Output rating)
7.5 11 15 18.5 22 30 37 45 55 75 90 110
Rated capacity (kVA)
*2
11 16 20 25 30 43 55 68 81 107 131 158
Rated voltage (V)
*3
Three-phase 200 to 240 V (with AVR function) Three-phase 200 to 230 V (with AVR function)
Rated current (A)
*4
31.8
(29)
46.2
(42)
59.4
(55)
74.8
(68)
88
(80)
115
(107)
146 180 215 283 346 415
Output ratings
Overload capability 120%-1 min
Voltage, frequency 200 to 240 V, 50/60 Hz
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5
, Frequency: +5 to -5%
Input power
Required capacity
(with DCR) (kVA)
*6
10 15 20 25 30 40 48 58 71 98 116 143
Torque (%)
*7
70% 15% 7 to 12%
Braking transistor Built-in
Built-in braking resistor
Braking time (s)
3.7 s 3.4 s
Braking
Duty cycle (%ED) 2.2 1.4
DC reactor (DCR) *8 Option Provided as standard
Applicable safety
standards
UL508C, C22.2 No.14, IEC/EN61800-5-1:2007
Enclosure (IEC60529) IP20, UL enclosed type IP00, UL open type
Cooling method Fan cooling
Weight / Mass (kg) 6.5 6.5 5.8 9.5 9.5 10 25 32 42 43 62 105
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 220 V for 200 V class series and 440 V for 400 V class
series.
*3 Output voltage cannot exceed the power supply voltage.
*4 To use the inverter with the carrier frequency of 3 kHz or more at the surrounding temperature of 40°C or higher, manage
the load so that the current comes to be within the rated ones enclosed in parentheses ( ) in continuous running.
*5 Voltage unbalance (%) = Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) × 67 (IEC/EN61800-3
If this value is 2 to 3%, use an optional AC reactor (ACR).
*6 Required when a DC reactor (DCR) is used.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fuji Electric Frenic Mega Series and is the answer not in the manual?

Fuji Electric Frenic Mega Series Specifications

General IconGeneral
BrandFuji Electric
ModelFrenic Mega Series
CategoryInverter
LanguageEnglish

Related product manuals