12.1 Standard Model 1 (Basic Type)
12-1
Chapter 12 SPECIFICATIONS
12.1 Standard Model 1 (Basic Type)
12.1.1 Three-phase 200 V class series
HD (High Duty)-mode inverters for heavy load
Item Specifications
Type (FRN***G1S-2J) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Nominal applied motor
(kW)
*1
(Output rating)
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Rated capacity (kVA)
*2
1.1 1.9 3.0 4.2 6.8 10 14 18 24 28 34 45 55 68 81 107 131
Rated voltage (V)
*3
Three-phase 200 to 240 V (with AVR function) Three-phase 200 to 230 V (with AVR function)
Rated current (A) 3 5 8 11 18 27 37 49 63 76 90 119 146 180 215 283 346
Output ratings
Overload capability 150%-1 min, 200%-3.0 s
Voltage, frequency 200 to 240 V, 50/60 Hz
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5
, Frequency: +5 to -5%
Input power
Required capacity
(with DCR) (kVA)
*6
0.6 1.2 2.2 3.1 5.2 7.4 10 15 20 25 30 40 48 58 71 98 116
Torque (%)
*7
150% 100% 20% 10 to 15%
Braking transistor Built-in -
Built-in braking resistor
Braking time (s)
5 s -
Braking
Duty cycle (%ED) 5 3 5 3 2 3 2 -
DC reactor (DCR)
*8
Option
Provided as
standard
Applicable safety
standards
UL508C, C22.2 No.14, IEC/EN61800-5-1:2007
Enclosure (IEC60529) IP20, UL enclosed type IP00, UL open type
Cooling method Natural cooling Fan cooling
Weight / Mass (kg) 1.7 2.0 2.8 3.0 3.0 6.5 6.5 5.8 9.5 9.5 10 25 32 42 43 62 105
LD (Low Duty)-mode inverters for light load
Item Specifications
Type (FRN***G1S-2J) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Nominal applied motor
(kW)
*1
(Output rating)
- 7.5 11 15 18.5 22 30 37 45 55 75 90 110
Rated capacity (kVA)
*2
- 11 16 20 25 30 43 55 68 81 107 131 158
Rated voltage (V)
*3
- Three-phase 200 to 240 V (with AVR function) Three-phase 200 to 230 V (with AVR function)
Rated current (A)
*4
-
31.8
(29)
46.2
(42)
59.4
(55)
74.8
(68)
88
(80)
115
(107)
146 180 215 283 346 415
Output ratings
Overload capability - 120%-1 min
Voltage, frequency - 200 to 240 V, 50/60 Hz
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
Allowable
voltage/frequency
- Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5
, Frequency: +5 to -5%
Input power
Required capacity
(with DCR) (kVA)
*6
- 10 15 20 25 30 40 48 58 71 98 116 143
Torque (%)
*7
- 70% 15% 7 to 12%
Braking transistor - Built-in -
Built-in braking resistor
Braking time (s)
- 3.7 s 3.4 s -
Braking
Duty cycle (%ED) - 2.2 1.4 -
DC reactor (DCR) *8 - Option Provided as standard
Applicable safety
standards
-
UL508C, C22.2 No.14, IEC/EN61800-5-1:2007
Enclosure (IEC60529) - IP20, UL enclosed type IP00, UL open type
Cooling method - Fan cooling
Weight / Mass (kg) - 6.5 6.5 5.8 9.5 9.5 10 25 32 42 43 62 105
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 220 V for 200 V class series and 440 V for 400 V class
series.
*3 Output voltage cannot exceed the power supply voltage.
*4 To use the inverter with the carrier frequency of 3 kHz or more at the surrounding temperature of 40°C or higher, manage
the load so that the current comes to be within the rated ones enclosed in parentheses ( ) in continuous running.
*5 Voltage unbalance (%) = Max. voltage (V) - Min. voltage (V) / Three-phase average voltage (V) × 67 (IEC/EN61800-3)
If this value is 2 to 3%, use an optional AC reactor (ACR).
*6 Required when a DC reactor (DCR) is used.